Scope of application
NT/NH1 fuse link, Rated voltage: 500V/690V AC, rated breaking capacity: 120kA, NT/NH1 fuse link current characteristics: gG, usually used as a protective device to prevent short circuits and circuit overloads (gG type). They can also be used as motor protection or short-circuit protection for semiconductor components/equipment.
NT/NH1 fuse link, Run under the following normal usage conditions without additional modifications. When the normal usage conditions are exceeded, some parameters may need to be adjusted or referenced if they are within the allowed usage range. If the allowed usage conditions are exceeded, please consult our company and conduct a work adaptability assessment and testing of the conditions. The recommended long-term current value should not exceed 80% of the rated current.
|
Model |
Rated Voltage (V) |
Rated current(A) |
Rated Breaking Capacity[kA) |
Rated dissipationpowerof fuse-link[w) |
|||
|
Base |
Fuse-Link |
AC500V |
AC690V |
DC440V |
|||
|
RT16-1 NH1 |
|
160 |
80,100.125,160,200,250 |
120 |
50 |
100 |
≤32W |
Components of fuses
The fuse is mainly composed of a cover plate, indicator, contact blade, fuse melting piece, filler, and ceramic body
Cover plate: Made of high-strength aluminum alloy. Surface embossing makes the product more aesthetically pleasing,
Knife contact point: The overall design of copper, rather than the riveted structure, has stronger performance and lower temperature rise.
Fuse fuse: Made of high-performance copper, with a more reasonable layout design and stronger breaking ability.
Packing: Select high-purity silica sand.
Fuse body: made of high-frequency ceramic
Here are some precautions:
Unpacking and inspection of fuses
After opening the box, the first thing to check is whether the nameplate of the fuse matches the markings on the packaging box, and then check whether the fasteners on the fuse are loose
Or if it falls off, check if there are cracks or fissures in the ceramic tube of the fuse, if there is any leakage of quartz sand inside the fuse, and if the fuse has been exposed to water
If immersion or invasion occurs, the fuse cannot be put into use and the manufacturer should be contacted in a timely manner
Certificate
CB CE
Packing data
Outer packaging size: 31 * 30 * 28cm
Net weight: 20.5kg Gross weight: 23kg
total; 48 pieces, number of inner boxes: 3 pieces
FAQ
Hot Tags: NT/NH1 fuse link, China NT/NH1 fuse link manufacturers, suppliers, factory, cutout fuse link, NH fuse link, NH hrc fuses, NH2 with Indicator Fuse Links, nt nh fuse link, NT NH3 Fuse Link