WebMay 8, 2023 · View attachment 148287. I think that recommendation is intended to prevent the situation where the SCC has solar attached, and then a battery connection is made and starts the SCC....
WebJun 3, 2020 · I have up to this point understood a fuse was necessary between the battery and the SCC, and that's what I've got. The marine fuse block and a 100a fuse to go with my solar 80a / 60...
WebApr 20, 2023 · Between the charge controller and solar panels (Solar Connector Inline Fuse) Between the battery bank and inverter (ANL Fuse Set + Fuse) SOLAR...
WebNov 29, 2022 · Let’s say your charge controller has a maximum current of 40Amps, then you need to select a wire based on 40Amps. 40A x 1.25= 50A. A wire that can carry 50A is 8AWG or 10mm². The...
WebFeb 21, 2021 · If Will has a 40A charge controller, then 50A fuse is ideal for that part of the circuit, it is 25% larger than maximum continuous load to avoid nuisance trips. As HRTKD says, if...
WebDec 2, 2019 · www.mobile-solarpower.com. I have a solution I am trying to get feedback on that uses a relay as described on this thread to cutoff the solar array from the controller if BMS detects...